ENGINEER ON WATCH:
- Change over the control level to ER
- Inform duty officer by phone about blackout and estimated time for engine recovery
- Stop the main engine
- Sound engineer alarm
- Start stand by diesel generator
- Switch on synchronoscope and main circuit breaker running DG on main switchboard
- Restart all pumps in following sequence:
- ME LO pump
- ME SW cooling pump
- ME FW cooling pump
- Piston cooling pump
- Boiler feed pump
- Check whether ME AUX blower is on auto mode
CHIEF ENGINEER:
- Check all ME service system parameters and reset ME shut down button
- Ring “DEAD SLOW AHEAD” by telegraph
- Upon positive replay from bridge – start ME
ENGINEERS:
- Check and restart all AUX systems
- Check and restart the boiler
- Check all running pumps in engine room for leakage and proper temperature
- Restart A/C compressor; domestic fridge (ECR); A/C cooling pump
EL. ENGINEER:
- Investigate reason of blackout to avoid reocurrence
- Switch on ESB LINK circuit breaker
- Stop emergency generator
- Restart all consumer’s breakers