Preparation and change over. Preparation and change over of the engine for the
bridge control should be made in accordance with the instructions issued by the engine builder. The following points should be noted: The pump station for the hydraulic amplifier is started to provide oil pressure in the amplifier.
The automatic stop piston valve must be turned to the "Service" position.
Control Panel.
Check that the test telegraph switches on the mimic diagram are in the "Normal" position.
Check also that the switch in the
engine speed test unit is in the "Tacho" position. If this switch is left in the "Test" position, the unit lamp will light up. If a start attempt is made, registration of the engine's turning will not take place and the tacho and repeated start supervision unit (TRS) will register the missing tacho signal, and after 6 sastart blocking and a tacho failure alarm will be initiated. If the control system is not furnished with a TRS Unit, starting air will be admitted until the pressure switch is activated.