If some photos / pictures / drawings are not loading, then we recommend to use VPN services!
Showing posts with label Reactive power. Show all posts
Showing posts with label Reactive power. Show all posts

02/04/2025

Automatic Voltage Regulator. Real power, Reactive power, Apparent power. KW, KVAR, KVA

In a DC analogy with batteries in parallel, only voltage needs to be controlled for proper load sharing. Similarly, in a mechanical AC analogy, only torque requires control. However, when paralleling AC generators, both variables — torque and excitation — must be properly managed.

Automatic Voltage Regulator. Real power, Reactive power, Apparent power. KW, KVAR, KVA

  • Torque control regulates the division of real power (kilowatts, kW).
  • Excitation control manages the division of reactive power (kilovolt-amperes reactive, kVAR).

Both must be precisely controlled to ensure stable and efficient generator operation.

Real power represents the actual work performed by the electrical energy generated. It is supplied by the prime mover in the form of torque, which the generator converts into electrical energy. This energy is then delivered to a load, where it is transformed into useful forms such as heat, light, or mechanical motion (e.g., in a motor).

Reactive power, on the other hand, is the power required by inductive or capacitive loads to store energy during each half-cycle. In the example shown in Drawing 10, the load is purely resistive, such as a heating element. Since no reactive power is needed at any point on the sine wave, the current remains directly proportional to the voltage at all times. Real power can be calculated using Ohm’s Law in this scenario.

If you want to motivate authors to continue creating content for engineers and ETOs, you can donate using the link: >>> BUY COFFEE
Thanks for the donation and see you on our projects!